메인콘텐츠 바로가기

HI AIR KOREA Co., Ltd.

KOREAN

HOME

INDUSTRY

DAMPER

FIRE DAMPER
(FOR NUCLEAR POWER PLANT)

HI AIR KOREA(HAK) FIRE DAMPERS for nuclear power plant can be installed at HVAC systems provided for various buildings of a nuclear power plant.

HAK FIRE DAMPERS are used to prevent the spread of fire inside the ductwork through fire-resistance rated walls and floors.

These dampers are available as safety related (SR) and non-safety related (NSR) items. Safety related dampers are fabricated with Q class components & dedicated commercial grade items, and verified for seismic qualification (SQ).

If necessary, they can be verified for environmental qualification (EQ).

  • FEATURES

    FIRE DAMPER

    • Design base
      1. 1. DA of ASME AG-1 (KEPIC MH)
      2. 2. IEEE 323
      3. 3. IEEE 344 (KEPIC END 2000)
      4. 4. UL 555
    • Static system, Curtain type, 3-hour rated and UL listed
    • Dynamic system, Curtain type, rated 2000 fpm/4.0 in.wc
    • Function type
      • Fusible link / 165℉ (74℃) / 350℉ (176℃)
      • Electro thermal link (ETL) / 165℉ (74℃)
    • Size
      • Single section maximum : 36" x 36"
      • Multi section (Module type) maximum : 108" x 108"
    • Installed in sleeves furnished by buyer
    • UL listed test
      • Fire endurance test and hose stream test
      • Salt spray exposure test
      • Spring closing force test
      • Cycling test
      • Dynamic closure test

    ※ Note : UL listed fire damper shall be installed with 165℉ ETL or 165℉ fusible link.
        (350℉ fusible link is used single section only)

    STANDARD CONSTRUCTION FOR FIRE DAMPER

    Part  Material 
    Frame  Carbon steel + Hot dip gal'v 
    Blade(Seat)  Carbon steel + Hot dip gal'v 
    Fusible link  Fusible or ETL (Electro thermal link) 

SALES MANAGER