HI AIR KOREA Co., Ltd.

KOREAN

HOME

INDUSTRY

DAMPER

SWING PANEL
(FOR NUCLEAR POWER PLANT)

HI AIR KOREA SWING PANEL for nuclear power plant can be installed at HVAC systems provided for various buildings of a nuclear power plant.

HAK SWING PANELS mitigates the impact of an internal or external explosion and prevents overpressure on major equipment inside the plant.

  • FEATURES

    SWING PANEL

    • Design base
      1. 1. ASME AG-1 (KEPIC-MH)
      2. 2. IEEE 344 (KEPIC END 2000)
    • Design maximum temperature : 360℉
    • Operation setting pressure
      • Out flow type : 0.45 ~ 0.5 psid
      • In flow type : 1.35 ~ 1.5 psid
    • Mounting type : Wall mount
    • Leakage classification in accordance with ASME AG-1, Appendix DA-1
      • Blade(seat) : Leakage class Ⅱ

    STANDARD CONSTRUCTION FOR SWING PANEL

    Part  Material  Finishing 
    Frame  Stainless steel  Passivation 
    Blades(Seat)  Stainless steel  Passivation 
    Shaft  Stainless steel  Passivation 
    Locking device  Stainless steel  Passivation 
    Blade seal  Silicon foam gasket 
    Linkage  Stainless steel  Passivation 